Standard Rack Assembly

– Fully sheeted duct furnaces mounted in a 16-gauge galvanized steel frame.
– Provides listed temperature rise and air side pressure drop performance.
– Each furnace includes an individual shutoff valve, flexible gas connector & union piped to properly sized supply header.
– Condensate drains pre-piped to a common header.
– Easy removal of any single duct furnace.
– All controls prewired to a sequencer for system control.
– Customer only needs to provide Power, “Call for Heat” and a 0-10 VDC signal.

Outdoor Venting Kit

– Vent riser assembly with integral rain cap.
– Provides proper venting of flue gases and prevents flue gas recirculation into burner combustion air supply.

Application Guidelines Product Specification User Guidelines OEM Instructions Submittal / Order Information

Note: You must be logged in to view CAD, Gas Train and Wiring Diagram files.
Model NumberPDF  Alt PDF  PDF of Gas TrainPDF of Wiring DiagramMax Input MBHMax Output MBHMin Input MBHMin Output MBHMax Avail. Turndown (Nat)Max Ind. HX Input# of HX'sMax CFMMax APD @ Min RiseMax Temp RiseMin CFMMin APD @ Max RiseDim ADim BDim CDim DWeight (Lbs.)
HDA-VHX-250-500-OPDFPDFPDFPDF500400504010 to 12502185190.8310037040.0446.13047.417490
HDA-VHX-300-600-OPDFPDFPDFPDF600480604810 to 13002222220.9710044440.0551.63047.417533
HDA-VHX-350-700-OPDFPDFPDFPDF700560705610 to 13502259261.0910051850.0659.13047.417587
HDA-VHX-400-800-OPDFPDFPDFPDF800640806410 to 14002296301.210059260.0665.73047.417640
HDA-VHX-300-900-OPDFPDFPDFPDF900720604815 to 13003333330.9710066670.05783047.417785
HDA-VHX-500-1000-OPDFPDFPDFPDF10008001008010 to 15002370371.3810074070.0778.63047.420733
HDA-VHX-350-1050-OPDFPDFPDFPDF1050840705615 to 13503388891.0910077780.0687.83047.417856
HDA-VHX-600-1200-OPDFPDFPDFPDF12009601209610 to 16002444441.5210088890.0891.63047.420773
HDA-VHX-400-1200-OPDFPDFPDFPDF1200960806415 to 14003444441.210088890.0697.53047.417936
HDA-VHX-500-1500-OPDFPDFPDFPDF150012001008015 to 15003555561.38100111110.071173047.4201076
HDA-VHX-600-1800-OPDFPDFPDFPDF180014401209615 to 16003666671.52100133330.081313047.4201136
Note: For Propane gas, turndown is 60% of stated natural gas turndown.